Notifications
You must be signed in to change notification settings - Fork 2
Example Heat exchanger
florian.stinner edited this page Jun 20, 2022
·
1 revision
Number | category | assignment | specification | BUDO |
---|---|---|---|---|
1-11 | subsystem | heat exchanger | - | HX |
1 | subsubsystem | pump | - | PU |
1 | medium 2nd specification | inlet | - | IN |
2 | subsubsystem | meter | heat | MET+H |
2 | medium | water | heating water | WS+H |
2 | medium 2nd specification | primary | - | PRIM |
2 | medium 3rd specification | inlet | - | IN |
2 | signal type | measured value | temperature | MEA+T |
3 | subsubsystem | meter | heat | MET+H |
3 | medium | water | heating water | WS+H |
3 | medium 2nd specification | secondary | - | SEC |
3 | medium 3rd specification | outlet | - | OUT |
3 | signal type | measured value | temperature | MEA+T |
4 | subsubsystem | valve | - | VAL |
4 | medium | water | heating water | WS+H |
4 | medium 2nd specification | secondary | - | SEC |
4 | medium 3rd specification | outlet | - | OUT |
4 | subsubsystem | pump | - | PU |
4 | medium | water | heating water | WS+H |
4 | medium 2nd specification | secondary | - | SEC |
4 | medium 3rd specification | outlet | - | OUT |
5 (example 1) | signal type | measured value | rotation speed | MEA+NROT |
5 (example 2) | signal type | controlled value | rotation speed | MEA+NROT |
5 (example 2) | signal type 2nd specification | maximum | - | MAX |
5 (example 3) | signal type | switching command | ready for operation | COM.SWI+OPR.RDY |
6 | subsubsystem | meter | heat | MET+H |
6 | medium | water | heating water | WS+H |
6 | medium 2nd specification | primary | - | PRIM |
7 | subsubsystem | meter | heat | MET+H |
7 | medium | water | heating water | WS+H |
7 | medium 2nd specification | secondary | - | SEC |
8 | subsubsystem | meter | heat | MET+H |
8 | medium | water | heating water | WS+H |
8 | medium 2nd specification | primary | - | PRIM |
8 | medium 3rd specification | outlet | - | OUT |
8 | signal type | measured value | volume flow | MEA+VF |
9 | subsubsystem | meter | heat | MET+H |
9 | medium | water | heating water | WS+H |
9 | medium 2nd specification | primary | - | PRIM |
9 | medium 3rd specification | outlet | - | OUT |
9 | signal type | measured value | temperature | MEA+T |
10 | subsubsystem | meter | heat | MET+H |
10 | medium | water | heating water | WS+H |
10 | medium 2nd specification | secondary | - | SEC |
10 | medium 3rd specification | inlet | - | IN |
10 | signal type | measured value | volume flow | MEA+VF |
11 | subsubsystem | meter | heat | MET+H |
11 | medium | water | heating water | WS+H |
11 | medium 2nd specification | secondary | - | SEC |
11 | medium 3rd specification | inlet | - | IN |
11 | signal type | measured value | temperature | MEA+T |