Fix IIR coefficient python script #964

Merged
merged 1 commit into from
Nov 11, 2024
Merged

Conversation

schmidf
Copy link

@schmidf schmidf commented Nov 11, 2024

Fixes #854. I checked the correctness of the coefficients using a Stabilizer with up-to-date firmware and a network analyzer.

The Stabilizer firmware expects "a" coefficients with negative signs.
Also fixed a typo in the highpass b0 coefficient.
Copy link
Member

@jordens jordens left a comment

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Ok as a temp fix, still pending the rewrite mentioned in the issue.

Proof by example (i.e. network analyzer) ultimately doesn't cut it but this is certainly an improvement.

@jordens
Copy link
Member

jordens commented Nov 11, 2024

Thanks!

@jordens jordens added this pull request to the merge queue Nov 11, 2024
Merged via the queue into quartiq:main with commit aa99010 Nov 11, 2024