242 changes: 240 additions & 2 deletions ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -145,6 +145,8 @@ REFM:
is_abstract: true
implements:
- MONITORING
opt_uses:
- high_zone_air_refrigerant_concentration_alarm
uses:
- zone_air_refrigerant_concentration_sensor

Expand Down Expand Up @@ -263,6 +265,8 @@ DSP:
opt_uses:
- discharge_air_temperature_sensor
- zone_air_relative_humidity_sensor
- high_zone_air_relative_humidity_alarm
- low_zone_air_relative_humidity_alarm
- failed_discharge_air_temperature_alarm
- failed_zone_air_temperature_alarm
- high_zone_air_temperature_alarm
Expand Down Expand Up @@ -1470,6 +1474,8 @@ EPC:
- exhaust_air_static_pressure_setpoint
opt_uses:
- exhaust_air_flowrate_sensor
- high_exhaust_air_static_pressure_alarm
- low_exhaust_air_static_pressure_alarm
implements:
- OPERATIONAL

Expand Down Expand Up @@ -1759,6 +1765,7 @@ CHWDC:
- cooling_thermal_power_capacity
- leaving_cooling_coil_temperature_sensor
- failed_discharge_air_temperature_alarm
- failed_chilled_water_valve_alarm
uses:
- chilled_water_valve_percentage_command
- discharge_air_temperature_sensor
Expand Down Expand Up @@ -1866,6 +1873,7 @@ CHWZC:
- leaving_cooling_coil_temperature_sensor
- failed_discharge_air_temperature_alarm
- failed_zone_air_temperature_alarm
- failed_chilled_water_valve_alarm
- high_zone_air_temperature_alarm
- low_zone_air_temperature_alarm
uses:
Expand Down Expand Up @@ -2702,6 +2710,7 @@ HWZC:
- failed_zone_air_temperature_alarm
- high_zone_air_temperature_alarm
- low_zone_air_temperature_alarm
- failed_heating_water_valve_alarm
uses:
- heating_water_valve_percentage_command
- zone_air_heating_temperature_setpoint
Expand Down Expand Up @@ -3139,6 +3148,8 @@ ECON:
opt_uses:
- low_limit_outside_air_damper_percentage_command
- outside_air_damper_percentage_sensor
- failed_outside_air_damper_alarm
- failed_outside_air_flowrate_alarm
- outside_air_flowrate_sensor
- outside_air_flowrate_setpoint
- outside_air_relative_humidity_sensor
Expand Down Expand Up @@ -3308,6 +3319,7 @@ VOADM:
- mixed_air_temperature_sensor
- outside_air_damper_percentage_sensor
- failed_mixed_air_temperature_alarm
- failed_outside_air_damper_alarm
uses:
- outside_air_damper_percentage_command
- outside_air_temperature_sensor
Expand All @@ -3332,6 +3344,7 @@ OAFM:
opt_uses:
- outside_air_damper_percentage_sensor
- outside_air_temperature_sensor
- failed_outside_air_flowrate_alarm
uses:
- outside_air_flowrate_sensor
implements:
Expand Down Expand Up @@ -3519,6 +3532,7 @@ BYPVPM:
is_abstract: true
opt_uses:
- bypass_valve_percentage_sensor
- failed_bypass_valve_alarm
uses:
- bypass_valve_percentage_command
implements:
Expand Down Expand Up @@ -3615,18 +3629,18 @@ CHWBZC:
- high_zone_air_temperature_alarm
- low_zone_air_temperature_alarm


CHWBYPVPM:
guid: "68cd5104-bf2e-48f3-8b88-c12192509393"
description: "Chilled water bypass valve percentage monitoring."
is_abstract: true
opt_uses:
- failed_chilled_water_bypass_valve_alarm
uses:
- chilled_water_bypass_valve_percentage_command
- chilled_water_bypass_valve_percentage_sensor
implements:
- MONITORING


MXVPM:
guid: "4bb25777-d661-4fd3-9f8f-a84b349ada87"
description: "Mixing valve percent monitoring."
Expand Down Expand Up @@ -4268,13 +4282,16 @@ SWISOVM:
- MONITORING
opt_uses:
- failed_isolation_valve_alarm
- failed_supply_water_isolation_valve_alarm
- local_override_isolation_valve_alarm


SWISOVPM:
guid: "33856563-ebe5-42ee-a928-e8b46d81772d"
description: "Supply side isolation valve monitoring."
is_abstract: true
opt_uses:
- failed_supply_water_isolation_valve_alarm
uses:
- supply_water_isolation_valve_percentage_command
- supply_water_isolation_valve_percentage_sensor
Expand All @@ -4286,6 +4303,8 @@ RWISOVM:
guid: "2d35bbb0-bcad-4f36-a8cb-0c9031d81886"
description: "Return side isolation valve monitoring."
is_abstract: true
opt_uses:
- failed_return_water_isolation_valve_alarm
uses:
- return_water_isolation_valve_command
- return_water_isolation_valve_status
Expand Down Expand Up @@ -4353,6 +4372,8 @@ CHWSWISOVM:
guid: "1a187792-767f-4132-9333-161c6db07ce4"
description: "Supply side isolation valve monitoring."
is_abstract: true
opt_uses:
- failed_chilled_supply_water_isolation_valve_alarm
uses:
- chilled_supply_water_isolation_valve_command
- chilled_supply_water_isolation_valve_status
Expand Down Expand Up @@ -4446,6 +4467,8 @@ CWRISOVM:
guid: "cb8b8c1e-30c2-48fc-b6c0-44d73468d994"
description: "Condensing water return isolation monitoring."
is_abstract: true
opt_uses:
- failed_condensing_return_water_isolation_valve_alarm
uses:
- condensing_return_water_isolation_valve_command
- condensing_return_water_isolation_valve_status
Expand All @@ -4457,6 +4480,8 @@ CWSISOVPM:
guid: "3221aa75-8df4-4964-82dd-9a5c59c3a73b"
description: "Condensing water supply isolation monitoring."
is_abstract: true
opt_uses:
- failed_condensing_supply_water_isolation_valve_alarm
uses:
- condensing_supply_water_isolation_valve_percentage_command
- condensing_supply_water_isolation_valve_percentage_sensor
Expand All @@ -4468,6 +4493,8 @@ CWSISOVM:
guid: "6284c4c0-1261-44f7-bebb-ab6aa11443ca"
description: "Condensing water supply isolation monitoring."
is_abstract: true
opt_uses:
- failed_condensing_supply_water_isolation_valve_alarm
uses:
- condensing_supply_water_isolation_valve_command
- condensing_supply_water_isolation_valve_status
Expand Down Expand Up @@ -6933,3 +6960,214 @@ PMDM:
- zone_air_pm10pt0_density_sensor
implements:
- MONITORING

HSWTC:
guid: "d9cf672c-8081-4e2b-9bba-599d8ac2bbd2"
description: "Heating supply water temperature control."
is_abstract: true
opt_uses:
- heating_supply_water_valve_percentage_sensor
- heating_return_water_temperature_sensor
- failed_heating_supply_water_valve_alarm
uses:
- heating_supply_water_valve_percentage_command
- heating_supply_water_temperature_sensor
- heating_supply_water_temperature_setpoint
implements:
- CONTROL

WSEBYPVPM:
guid: "70e5c471-4b14-4d81-8bf2-ec8dcfbb29dd"
description: "Water side economizer bypass valve monitoring."
is_abstract: true
opt_uses:
- economizer_bypass_valve_percentage_sensor
- failed_economizer_bypass_valve_alarm
uses:
- economizer_bypass_valve_percentage_command
implements:
- MONITORING

FSWISOVM:
guid: "58f0a5fb-fc3e-4384-91b1-ba7db225ec6c"
description: "Filtration supply isolation valve monitoring."
is_abstract: true
uses:
- filtration_supply_water_isolation_valve_command
implements:
- MONITORING

FRWISOVM:
guid: "6d8a9548-5879-493a-a991-cd3ed3eb80ac"
description: "Filtration return isolation valve monitoring."
is_abstract: true
uses:
- filtration_return_water_isolation_valve_command
implements:
- MONITORING

PRWFRM:
guid: "d24ca9da-2897-42ba-9010-59b65971613d"
description: "Primary supply water flowrate monitoring"
uses:
- primary_supply_water_flowrate_sensor
implements:
- MONITORING

SEWFRM:
guid: "de0de0fc-e634-4bbc-8ecc-4d413614c84d"
description: "Secondary supply water flowrate monitoring"
uses:
- secondary_supply_water_flowrate_sensor
implements:
- MONITORING

MWFRM:
guid: "c7683a09-8379-4951-aa1e-e5edc4e098cb"
description: "Make-up water flowrate monitoring."
is_abstract: true
opt_uses:
- failed_makeup_water_flowrate_alarm
uses:
- makeup_water_flowrate_sensor
implements:
- MONITORING

BWFRM:
guid: "2be49785-9467-4ddb-8aa8-9c2b77277d29"
description: "Blowdown water flowrate monitoring."
is_abstract: true
opt_uses:
- failed_blowdown_water_flowrate_alarm
uses:
- blowdown_water_flowrate_sensor
implements:
- MONITORING

DX3SCHWC:
guid: "917e4514-ed4d-468c-8a81-44d29a143935"
description: "Three compressor run control on chilled supply water side."
is_abstract: true
uses:
- compressor_run_command_1
- compressor_run_command_2
- compressor_run_command_3
- compressor_run_status_1
- compressor_run_status_2
- compressor_run_status_3
- chilled_supply_water_temperature_sensor
- chilled_supply_water_temperature_setpoint
implements:
- CONTROL

CWBYPVPM:
guid: "88212fc0-0ddb-4cd9-99a3-e646dd20d528"
description: "Condensing water bypass valve percentage monitoring."
is_abstract: true
opt_uses:
- failed_condensing_water_bypass_valve_alarm
uses:
- condensing_water_bypass_valve_percentage_command
- condensing_water_bypass_valve_percentage_sensor
implements:
- MONITORING

HWBYPVPM:
guid: "38b01712-d458-4e5c-bf41-71107ebe8ecd"
description: "Heating water bypass valve percentage monitoring."
is_abstract: true
opt_uses:
- failed_heating_water_bypass_valve_alarm
uses:
- heating_water_bypass_valve_percentage_command
- heating_water_bypass_valve_percentage_sensor
implements:
- MONITORING

HWBYPVM:
guid: "c4a7009c-1ccb-4162-8761-fd1e0acc5169"
description: "Heating water bypass valve monitoring."
is_abstract: true
opt_uses:
- failed_heating_water_bypass_valve_alarm
uses:
- heating_water_bypass_valve_command
- heating_water_bypass_valve_status
implements:
- MONITORING

HWDPC:
guid: "46009d2e-eee4-4e0a-a775-157fa7193983"
description: "Heating water differential pressure control."
is_abstract: true
uses:
- heating_water_differential_pressure_sensor
- heating_water_differential_pressure_setpoint
implements:
- OPERATIONAL

HP6SWC:
guid: "5d2c6d94-ad64-41ef-bce0-78a9b40532b1"
description: "Six-compressor heat pump control on supply water side."
is_abstract: true
opt_uses:
- heating_percentage_command
- heating_thermal_power_capacity
- high_supply_water_temperature_alarm
- low_supply_water_temperature_alarm
uses:
- compressor_run_command_1
- compressor_run_command_2
- compressor_run_command_3
- compressor_run_command_4
- compressor_run_command_5
- compressor_run_command_6
- compressor_run_status_1
- compressor_run_status_2
- compressor_run_status_3
- compressor_run_status_4
- compressor_run_status_5
- compressor_run_status_6
- supply_water_temperature_sensor
- supply_water_temperature_setpoint
implements:
- CONTROL

CPC2X:
guid: "a45b771d-0bc2-49a4-8a4f-5e3287f65ff0"
description: "Circulation control for 2 pumps."
is_abstract: true
uses:
- circulation_pump_run_command_1
- circulation_pump_run_status_1
- circulation_pump_run_command_2
- circulation_pump_run_status_2

SDHC:
guid: "de065843-b1a9-4d2e-b751-31d7af8e8991"
description: "Supply dehumidification control with a temperature setpoint."
is_abstract: true
opt_uses:
- dehumidification_percentage_command
- zone_air_dewpoint_temperature_sensor
- supply_air_relative_humidity_sensor
- failed_dehumidifier_alarm
uses:
- dehumidification_run_command
- leaving_dehumidifier_temperature_sensor
- leaving_dehumidifier_temperature_setpoint
implements:
- CONTROL

FPHC:
guid: "bdd89332-3303-420d-a13c-ee38c398d9ff"
description: "Four pipe heating and cooling control for radiant panels."
is_abstract: true
opt_uses:
- heating_supply_water_isolation_valve_command
- chilled_supply_water_isolation_valve_command
- heating_water_valve_percentage_sensor
- chilled_water_valve_percentage_sensor
uses:
- heating_water_valve_percentage_command
- chilled_water_valve_percentage_command