Skip to content
New issue

Have a question about this project? Sign up for a free GitHub account to open an issue and contact its maintainers and the community.

By clicking “Sign up for GitHub”, you agree to our terms of service and privacy statement. We’ll occasionally send you account related emails.

Already on GitHub? Sign in to your account

Inlet water temp change #480

Open
MathieuLH44 opened this issue Nov 22, 2024 · 13 comments
Open

Inlet water temp change #480

MathieuLH44 opened this issue Nov 22, 2024 · 13 comments

Comments

@MathieuLH44
Copy link

Hi,

I have an issue about the Inlet water temp.
Sometimes, when the weather is cold, this setting value change too low (lower value asked 40°C, issue value 35°C)

This happen online when I allow the external thermostat

Do you had the same issue ? Maybe is a setting to change ?

@HaiQ31
Copy link

HaiQ31 commented Nov 24, 2024

I am not sure whether I get your question. Where do you see the correct value und where the one too low? Do you mean, that your inlet temp. value provided by espaltherma does not show the correct value? How is the external thermostat related to espaltherma?

@MathieuLH44
Copy link
Author

I set a LW (48°C at -5 and 40°C at 20), but, the inlet temperature drop to about 35°C (by ESPaltherma), and this value is on the screen of the control panel
But this happen only when I use the external thermostat

Capture d'écran 2024-11-24 113154
Capture d'écran 2024-11-24 113144

When this happen, the pump shorts cycling, so I think it's not the best for the durability

@HaiQ31
Copy link

HaiQ31 commented Nov 24, 2024

I still have questions. As I understand so far:

  • You use the two-point curve for weather-dependent control.
  • P1 equals (20°C, 40°C) with X: ambient, Y: LW setpoint
  • P2 equals (-5°C, 45°C)
  • reglage loi d'eau A = LWT ?
  • reglage loi d'eau P = RWT ?

what I see:

  • most of the time your LW and RW are constant.
  • sometimes the RW temp rises but the LW temp does not
  • sometimes the RW remp rises and the LW temp does as well
  • the pump is running for short periods most of the time.
  • the pump goes off when EXT rises

what I guess:

  • LWT and RWT mixed up? Leaving water temp should be higher then return. Otherwise its cooling.
  • you have valves on the emitters that control the flow through the emitters.
  • your pump is set to scan mode (not sure how its called in the english manual).
    -> these two would mean, that your HP does not know the heat demand since no room sensor is connected to the HP itself. Therefore the pump starts every 3min and checks whether RW is getting cold or not. If so the compressor starts, otherwise pump goes back off and waits another 3min. (3-6AM looks like this)
  • in case of demand (a few minutes around 18:30 o'clock) both LW and RW rises, but pump goes back off. This happens when EXT Temp rises. Is the highest ambient temp. for heating set to a value near that what EXT shows? This would force the pump off. (two-point curve does not influence this!)

what I miss:

  • LW set point (this should show you the calculated set point at the time)
  • operation on/off of compressor (can be seen with compressor speed)

I'd be happy to think things over with you, but what I see here is not related to espaltherma sensor. Espaltherma is just the messanger here of what your HP is doing.

edit: add links to *.h files as an example

@MathieuLH44
Copy link
Author

I think that the ;
loi d'eau P is for the main area
loi d'eau A is for the second area (not active)
But i'm not sure
What do you mean when you say RWT ?

I add a picture of the settings (I tried some little change on the temperatures)
PXL_20241124_202816175

Yes, the LW is constant, but it's under the wanted value

Yesterday, the pump works well after a restart (8h30)
Capture d'écran 2024-11-24 213702

@HaiQ31
Copy link

HaiQ31 commented Nov 25, 2024

ah okay. I estimated "A" stands for "Avance" which I translated with "leaving water" (LW, leaving the heat pump to the emitter) and "P" stands for "prise d'eau" which I translated with "returning water" (RW, returning water from the emitter back to the heat pump). With "RWT" I mean returning water temperature.
To figure out whether something is wrong here or not, I think we need leaving water temperatur and returning water temperatur time series. I add a figure that shows what I mean: blue is the set point for LWT [sic] at the time, yellow is LWT and orange is RWT. You see a lot of peaks over the set point and valleys bellow it.

Temperatures
What you can't see is that the flow rate of the water. This shows the second figure. As you can see, peaks only occure when flow is above 0 L/min. But not every time. This is because the compressor does not heat everytime.
flowrate
You can see this in the last figure
compressore speed
Only when heat demand exists the compressor switches on. If no heat demand is left, it goes back off. If you look on the first figure you can see that in the peaks, the spread between RWT and LWT is lower than 4K. It's about 1,5K. For the HP that means that the heat is not needed. To figure out whether there is something wrong at yours, we need all this information.

At 8.30 your water pump went off. As I mentioned: your water pump starts every now and then to scan if heating demand exists. Without the state of your compressor (the actual heat generator), we can't see whether your heating system tries to heat or not.

Do you experience any issue with the heating system, like cold rooms or something else that makes you think something is wrong with it?

edit: add figures as example

@MathieuLH44
Copy link
Author

I add the temperature of the leaving water (orange) and of the return temperature (purple)

I restarted the heat pump at 8:30
Capture d'écran 2024-11-26 220738

Capture d'écran 2024-11-26 221025
Capture d'écran 2024-11-26 221210

I see that your heat pump do a lot of short cycle, but, I think it's not good for the durability

Do you speak french ?

@HaiQ31
Copy link

HaiQ31 commented Nov 27, 2024

I don‘t speak french. I just played around with deepl;)

I see what you mean before the power cycle. But this is not necessarily faulty. If yellow means the set Point of LWT everything works as intended. But why your HP lowers the set Point to this value can‘t be seen here. Do you have schedules set up? Are there further external inputs i.e. room sensors, smart grid,…

After the power cycle, your LWT (orange) looks good and is near the set point. The spread between LWT and RWT looks good as well.

As a side note: that the HP says it is in heating mode does not necessarily mean that it‘s actually producing heat. Depending on your installation, It just means that it performs all necessary operarions and measurments to produce heat (including but not limited to produce heat)

you are right, the HP short-cycles a lot. Since this is because of demand lower than the minimum heating power and no storage it is hard to reduce these.

@MathieuLH44
Copy link
Author

ok, i believed

For me, as the leaving temperature is lower than the wanted temperature, the is an issue, moreover, when this happen, the heat pump is heating for hours, even if the ambiant temperature is reached
If the LWT is according with the set point after the reset, it's because there is an issue for me

With this heat pump, the domestic heat water is a priority

@MathieuLH44
Copy link
Author

During the night, the issue appeared again

I add a curve of the external thermostat (last one) When there is an orange area, the trigger ask for heating. So, the heat pump looks like to ask heating, event if the external trigger doesn't ask it

Capture d'écran 2024-11-29 170134

Capture d'écran 2024-11-29 170149

Capture d'écran 2024-11-29 170202

@HaiQ31
Copy link

HaiQ31 commented Nov 29, 2024

Can you add a curve or a Sketch or so to show what you would expect to see instead? Without knowledge how your heating system and its control is set up it is difficult to anticipate what the expected behaviour would looks like.

for what I see the HP is heating since the room gets warmer with constant ambient temperature until it stops at around 11am.

@MathieuLH44
Copy link
Author

On the last graph, the yellow curve is the wanted temperature in the house
The temperature that I asked are :
0 - 6:20 : 19.5°C
6:20 - 7:00 : 20.5°C
7:00 - 15:40 : 18.5
15:40 - 0:00 : 20.5

I add the law water here
Capture d'écran 2024-11-29 183031

@HaiQ31
Copy link

HaiQ31 commented Nov 29, 2024

You configured the law water at the HP interface like you showed in the first picture of this post, right?

Until 1.30o'clock and after 10.45o'clock it locks fine. It looks like something overrules the law water curve in between. Maybe this is the reason for the peaks, that random occure. Do you have an idea what that could be? Is there an energy-saving-rule at night? Do you have room sensors? Where do you set the temperature schedule you mentioned here:

The temperature that I asked are :
0 - 6:20 : 19.5°C
6:20 - 7:00 : 20.5°C
7:00 - 15:40 : 18.5
15:40 - 0:00 : 20.5

Also at the HP interface?

@MathieuLH44
Copy link
Author

I tried to change a little the values, but the settings were the same

The temperature by hours are configurated on HA
For me, the curve between 1:30 and 10:45 is du to the outside temperature, that is too low
For exemple, when the outsite temperature is about 10°C, there is no problems

Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment
Labels
None yet
Projects
None yet
Development

No branches or pull requests

2 participants