245 gas workflows template updates #246

Merged
merged 7 commits into from
Dec 11, 2024
22 changes: 12 additions & 10 deletions src/templates/ira_doe_workflow_high_efficiency_gas_furnace.mdx
Original file line number Diff line number Diff line change
Expand Up @@ -22,7 +22,7 @@
- To show that the vent is far enough away from windows, doors, soffits, eaves, crawlspace vents, and air intakes. All clearance requirements are in accordance with ANZI Z21 .10.3 and the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 and CGA 8149.1 National Gas and Propane Installation Code.
- To show that the wall penetration for the vent has been flashed correctly.
- Install the termination high enough so that snow drifts won’t block the vent.
- Install termination fittings in a manner to prevent short circuit of air from exhaust to intake.
- Install termination fittings in a manner to prevent short circuit of air from exhaust to intake.
- The installation of bird screens are recommended.
</PhotoInput>

Expand All @@ -48,7 +48,7 @@
</PhotoInput>

<PhotoInput id="air_flow_measurement_photo" label="Airflow Measurement – Photo">
Take a photo of the airflow measurement. Measurements obtained by a TrueFlow grid, air flow capture hood, or balometer are valid. Condensing furnaces require approximately 150 CFM per 10,000 Btu input. Make adjustments to the fan setting as needed to achieve target airflow.
Take a photo of the airflow measurement. Measurements obtained by a TrueFlow grid, air flow capture hood, or balometer are valid. Condensing furnaces require approximately 150 CFM per 10,000 Btu input. Make adjustments to the fan setting as needed to achieve target airflow.
</PhotoInput>

<PhotoInput id="air_filter_photo" label="Air Filter – Photo">
Expand All @@ -64,13 +64,14 @@
Take a representative photo of the electronic methane leak detector while it is testing a gas connection. Please take the time to check all the other gas connections.
</PhotoInput>

<PhotoInput id="inlet_gas_pressure_manometer_photo" label="Manometer Showing Inlet Gas pressure – Photo">
Take a photo of the manometer measuring the inlet gas pressure.
<PhotoInput id="outlet_gas_pressure_manometer_photo" label="Manometer Showing Outlet Gas pressure – Photo">
Take a photo of the manometer measuring the outlet gas pressure for single, two, and three speed gas furnaces. Skip this photo prompt if the furnace is a modulating firing rate furnaces.
</PhotoInput>

<PhotoInput id="combustion_analysis_results_photo" label="Combustion Analysis Results – Photo">
Take a photo of the combustion analysis results. Refer to local regulations on how to do this test, from the outside vent, or drilling into the PVC pipe. Some equipment may have a test port for this purpose.
</PhotoInput>

</Tab>
<Tab eventKey="report" title="Report">
<PrintSection label="Print Report">
Expand All @@ -81,9 +82,9 @@
<ProjectInfoReport {...props} />

## About the Report

The photos in this report are intended to document the critical details of upgrading to a high efficiency gas furnace installation.

### General
<Photo id="nameplate_photo" label="Nameplate – Photo" required>
Photo of the nameplate of the new system
Expand Down Expand Up @@ -114,13 +115,13 @@
### Airflow
<Photo id="manometer_external_static_pressure_photo" label="Manometer Showing External Static Pressure – Photo" required>
Photo of the manometer showing the total external static pressure measurement.
The total external static pressure should ideally be less than 0.5 i.w.c. It should not be above 0.8 i.w.c.
The total external static pressure should ideally be less than 0.5 i.w.c. It should not be above 0.8 i.w.c.
</Photo>

<Photo id="air_flow_measurement_photo" label="Airflow Measurement – Photo" required>
Photo of the airflow measurement. Condensing furnaces require approximately 150 CFM per 10,000 Btu input.
</Photo>

<Photo id="air_filter_photo" label="Air Filter – Photo" required>
Photo of the air filter. If the system has an air filter slot, the door should have a gasket. If the system has an air filter grille, the perimeter should be sealed to minimize air bypassing the filter.
</Photo>
Expand All @@ -134,8 +135,8 @@
Photo of the electronic methane leak detector while it is testing a gas connection
</Photo>

<Photo id="inlet_gas_pressure_monometer_photo" label="Monometer Showing Inlet Gas pressure – Photo" required>
Photo of the manometer measuring the inlet gas pressure
<Photo id="outlet_gas_pressure_manometer_photo" label="Manometer Showing Outlet Gas pressure – Photo" required>
Take a photo of the manometer measuring the outlet gas pressure for single, two, and three speed gas furnaces. Skip this photo prompt if the furnace is a modulating firing rate furnaces.
</Photo>

<Photo id="combustion_analysis_results_photo" label="Combustion Analysis Results – Photo" required>
Expand All @@ -154,5 +155,6 @@
<PDFRenderer id="manual_j_file" label="" />

</PrintSection>

</Tab>
</Tabs>
Original file line number Diff line number Diff line change
Expand Up @@ -7,7 +7,7 @@
<FileInput id="manual_j_file" label="PDF of Manual J Load Calculation - File">
Attach a PDF of the Manual J load calculation
</FileInput>

<PhotoInput id="nameplate_photo" label="Nameplate – Photo">
Take a photo of the nameplate.
</PhotoInput>
Expand All @@ -27,7 +27,7 @@
</PhotoInput>

<PhotoInput id="system_layout_diagram_photo" label="System Layout Diagram – Photo">
Take a photo of the system layout diagram. This can be a photo of a sketch, CAD drawing, or the diagram in the installation that matches the field installation setup
Take a photo of the system layout diagram. This can be a photo of a sketch, CAD drawing, or the diagram in the installation that matches the field installation setup
</PhotoInput>

## Venting
Expand All @@ -36,7 +36,7 @@
- To show that the vent is far enough away from windows, doors, soffits, eaves, crawlspace vents, and air intakes. All clearance requirements are in accordance with ANZI Z21 .10.3 and the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 and CGA 8149.1 National Gas and Propane Installation Code.
- To show that the wall penetration for the vent has been flashed correctly.
- Install the termination high enough so that snow drifts won’t block the vent.
- Install termination fittings in a manner to prevent short circuit of air from exhaust to intake.
- Install termination fittings in a manner to prevent short circuit of air from exhaust to intake.
- The installation of bird screens are recommended
</PhotoInput>

Expand All @@ -58,19 +58,15 @@
Take a representative photo of the electronic methane leak detector while it is testing a gas connection. Please take the time to check all the other gas connections.
</PhotoInput>

<PhotoInput id="inlet_gas_pressure_manometer_photo" label="Manometer Showing Inlet Gas pressure – Photo">
Take a photo of the manometer measuring the inlet gas pressure.
</PhotoInput>

<PhotoInput id="combustion_analysis_results_photo" label="Combustion Analysis Results – Photo">
Take a photo of the combustion analysis results. Refer to local regulations on how to do this tests, from the outside vent, or drilling into the PVC pipe. Some equipment may have a test port for this purpose.
</PhotoInput>

## Condensate
<PhotoInput id="condensate_management_piping_photo" label="Condensate management Piping – Photo">
Take a photo of the condensate management piping.
Take a photo of the condensate management piping.
- Photo must include the connections to the combustion air inlet moisture trap, acid neutralizer, secondary drain pan, and condensate pump if used.
- Note, some units have built in traps while others require an external trap. Systems with a built in trap may need the trap to be filled with water prior to start up to prevent the escape of combustion gases.
- Note, some units have built in traps while others require an external trap. Systems with a built in trap may need the trap to be filled with water prior to start up to prevent the escape of combustion gases.
</PhotoInput>

## Hydronics and Controls
Expand All @@ -79,16 +75,17 @@
</PhotoInput>

<PhotoInput id="heating_curve_coldest_outdoor_photo" label="Heating Curve Selected Setting for the Coldest Outdoor Temperature Day – Photo">
Take a photo of the heating curve selected setting for the coldest outdoor temperature day.
Take a photo of the heating curve selected setting for the coldest outdoor temperature day.
</PhotoInput>

<PhotoInput id="heating_curve_warmest_outdoor_photo" label="Heating Curve Selected Setting for the Warmest Outdoor Temperature Day – Photo">
Take a photo of the heating curve selected setting for the warmest outdoor temperature day.
Take a photo of the heating curve selected setting for the warmest outdoor temperature day.
</PhotoInput>

<NumberInput label="Hydronic loop’s pressure loss (feet of head)" min={0} path="hydronic_loop_pressure_loss" />

<NumberInput label="Setting percent maximum pump speed" min={0} path="max_pump_speed_percent" />

</Tab>
<Tab eventKey="report" title="Report">
<PrintSection label="Print Report">
Expand All @@ -99,9 +96,9 @@
<ProjectInfoReport {...props} />

## About the Report

The photos in this report are intended to document the critical details of upgrading to a high efficiency modulating boiler installation.

### General
<Photo id="nameplate_photo" label="Nameplate – Photo" required>
Photo of the nameplate of the new system
Expand Down Expand Up @@ -142,17 +139,13 @@
Photo of the electronic methane leak detector
</Photo>

<Photo id="inlet_gas_pressure_manometer_photo" label="Manometer Showing Inlet Gas pressure – Photo" required>
Photo of the manometer measuring the inlet gas pressure
</Photo>

<Photo id="combustion_analysis_results_photo" label="Combustion Analysis Results – Photo" required>
Photo of the combustion analysis results
</Photo>

### Condensate
<Photo id="condensate_management_piping_photo" label="Condensate management Piping – Photo" required>
Photo of the condensate management piping
Photo of the condensate management piping
</Photo>

### Hydronics and Controls
Expand All @@ -161,15 +154,15 @@
</Photo>

<Photo id="heating_curve_coldest_outdoor_photo" label="Heating Curve Selected Setting for the Coldest Outdoor Temperature Day – Photo" required>
Photo of the heating curve selected setting for the coldest outdoor temperature day
Photo of the heating curve selected setting for the coldest outdoor temperature day
</Photo>

<Photo id="heating_curve_warmest_outdoor_photo" label="Heating Curve Selected Setting for the Warmest Outdoor Temperature Day – Photo" required>
Photo of the heating curve selected setting for the warmest outdoor temperature day
Photo of the heating curve selected setting for the warmest outdoor temperature day
</Photo>

Hydronic loop’s pressure loss (feet of head): { props.data?.hydronic_loop_pressure_loss ? props.data?.hydronic_loop_pressure_loss : null } ft

For the integrated/primary circulation pump, percent of the maximum pump speed was set to { props.data?.max_pump_speed_percent ? props.data?.max_pump_speed_percent : null }%

{
Expand All @@ -184,5 +177,6 @@
<PDFRenderer id="manual_j_file" label="" />

</PrintSection>

</Tab>
</Tabs>
18 changes: 6 additions & 12 deletions src/templates/ira_doe_workflow_high_efficiency_water_heater.mdx
Original file line number Diff line number Diff line change
Expand Up @@ -13,7 +13,7 @@
</PhotoInput>

<PhotoInput id="installation_location_at_completion_photo" label="Installation Location at Completion – Photo">
Take a wide-angle photo of the installation location at completion.
Take a wide-angle photo of the installation location at completion.
- To show that there are no adjacent hazards, if installed in a garage this photo would show that the installation is at least 18 in. above the floor and protected from vehicle damage.
- To show the water pipes have been insulated, especially the hot water pipe and recirculation lines if present.
- To show the air inlet air filter has been clearly labeled for periodic inspection
Expand All @@ -27,7 +27,7 @@
- To show that the vent is far enough away from windows, doors, soffits, eaves, crawlspace vents, and air intakes. All clearance requirements are in accordance with ANZI Z21 .10.3 and the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 and CGA 8149.1 National Gas and Propane Installation Code.
- To show that the wall penetration for the vent has been flashed correctly.
- Install the termination high enough so that snow drifts won’t block the vent.
- Install termination fittings in a manner to prevent short circuit of air from exhaust to intake.
- Install termination fittings in a manner to prevent short circuit of air from exhaust to intake.
- The installation of bird screens are recommended
</PhotoInput>

Expand All @@ -54,13 +54,10 @@
Take a representative photo of the electronic methane leak detector while it is testing a gas connection. Please take the time to check all the other gas connections.
</PhotoInput>

<PhotoInput id="inlet_gas_pressure_manometer_photo" label="Manometer Showing Inlet Gas pressure – Photo">
Take a photo of the manometer measuring the inlet gas pressure.
</PhotoInput>

<PhotoInput id="combustion_analysis_results_photo" label="Combustion Analysis Results – Photo">
Take a photo of the combustion analysis results. Refer to local regulations on how to do this tests, from the outside vent, or drilling into the PVC pipe. Some equipment may have a test port for this purpose.
</PhotoInput>

</Tab>
<Tab eventKey="report" title="Report">
<PrintSection label="Print Report">
Expand All @@ -71,9 +68,9 @@
<ProjectInfoReport {...props} />

## About the Report

The photos in this report are intended to document the critical details of upgrading to a high efficiency tankless water heater installation.

### General
<Photo id="nameplate_photo" label="Nameplate – Photo" required>
Photo of the nameplate of the new system
Expand Down Expand Up @@ -114,14 +111,11 @@
Photo of the electronic methane leak detector while it is testing a gas connection
</Photo>

<Photo id="inlet_gas_pressure_manometer_photo" label="Manometer Showing Inlet Gas pressure – Photo" required>
Photo of the manometer measuring the inlet gas pressure
</Photo>

<Photo id="combustion_analysis_results_photo" label="Combustion Analysis Results – Photo" required>
Photo of the combustion analysis results
</Photo>

</PrintSection>