import serial
import time
import modbus_tk
import modbus_tk.defines as cst
from modbus_tk import modbus_rtu
"""定义地址"""
sys_db_stats = {4096: ['设备工作状态', 1, ''], 4098: ['室内风机状态', 1, ''], 4100: ['室外风机状态', 1, ''], 4102: ['压缩机状态', 1, ''], 4104: ['回风温度', 305, ''], 4110: ['冷凝器温度', 303, ''], 4114: ['内风机转速', 0, ''], 4116: ['外风机转速', 0, ''], 4120: ['直流输入电压', 542, ''], 4124: ['设备运行时间', 0, ''], 4128: ['压缩机运行时间', 0, ''], 4136: ['压缩机动作次数', '', ''], 7: ['通讯地址', '', ''], 8: ['通信速率', '', ''], 10: ['设定温度', '', ''], 12: ['设定回差', '', ''], 14: ['高温警告点', '', ''], 16: [
'低温警告点', '', ''], 18: ['直流过压警告', '', ''], 20: ['直流过压警告', '', ''], 28: ['加热器启动温度', '', ''], 30: ['加热器启动回差', '', ''], 768: ['高温告警', '', ''], 769: ['内风机故障告警', '', ''], 770: ['外风机告警', '', ''], 771: ['压缩机故障告警', '', ''], 772: ['内回风温度传感器告警', '', ''], 773: ['系统高压力告警', '', ''], 774: ['低温告警', '', ''], 775: ['直流过压告警', '', ''], 776: ['直流欠压告警', '', ''], 780: ['蒸发器温度传感器故障', '', ''], 781: ['冷凝器温度传感器故障', '', ''], 782: ['环境温度传感器故障', '', ''], 783: ['蒸发器冻结报警', '', '']}
temper = [0X1008, 0X100E, 0X1010, 0X0A, 0X0C,
0X0E, 0X10, 0X1C, 0X1E]
vote = [0X1018, 0X12, 0X14]
mode = [0X1000, 0X1002, 0X1004, 0X1006]
def mod(start, num, PORT='com6'):
red = []
read = {}
alarm = ""
try:
# 设定串口为从站
master = modbus_rtu.RtuMaster(serial.Serial(
port=PORT, baudrate=9600, bytesize=8, parity="N", stopbits=1))
master.set_timeout(1)
master.set_verbose(True)
# 读保持寄存器
red = master.execute(21, cst.READ_HOLDING_REGISTERS,
start, num) # 这里修改需要读取的功能代码
alarm = 0
# print(red)
for i in red:
read[start] = i
start += 1
return read, alarm
except Exception as exc:
alarm = (str(exc))
def data_pro():
"""处理取到数据的显示"""
for i in sys_db_stats:
if i in temper:
tt = str(sys_db_stats[i][1]/10) + '℃' # 温度数据
sys_db_stats[i][2] = tt
elif i in vote:
tt = str(sys_db_stats[i][1]/10) + 'V' # 电压数据
sys_db_stats[i][2] = tt
elif i in mode:
if sys_db_stats[i][1] == 1:
sys_db_stats[i][2] = '待机'
elif sys_db_stats[i][1] == 2:
sys_db_stats[i][2] = '运行'
elif sys_db_stats[i][1] == 3:
sys_db_stats[i][2] = '故障'
elif i >= 768 and i <= 784:
if sys_db_stats[i][1] == 0:
sys_db_stats[i][2] = '正常'
elif sys_db_stats[i][1] == 1:
sys_db_stats[i][2] = '告警'
else:
sys_db_stats[i][2] = sys_db_stats[i][1]
return sys_db_stats
def rtu_date_read():
"""从设备读取数据并更新数据库"""
secqus = [1, 2, 3]
for i in secqus:
if i == 1:
db_stats = mod(0x1000, 41)[0] # 读状态数据
elif i == 2:
db_stats = mod(0x07, 24)[0] # 读取设置数据
elif i == 3:
db_stats = mod(0x300, 16)[0] # 读取告警状态
for i in db_stats:
if i in sys_db_stats:
sys_db_stats[i][1] = db_stats[i]
data_pro()
def mod_crtl(PORT='com6'):
master = modbus_rtu.RtuMaster(serial.Serial(
port=PORT, baudrate=9600, bytesize=8, parity="N", stopbits=1))
master.set_timeout(1)
master.set_verbose(True)
master.execute(21, cst.WRITE_SINGLE_REGISTER, 10, output_value=350)
mod_crtl()
rtu_date_read()
for i in sys_db_stats:
print (str(sys_db_stats[i][0]) + ':' + '\t' + str(sys_db_stats[i][2]))