Notifications
You must be signed in to change notification settings - Fork 0
/
IEEE_thermal_model.m
617 lines (592 loc) · 29.4 KB
/
IEEE_thermal_model.m
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378
379
380
381
382
383
384
385
386
387
388
389
390
391
392
393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
441
442
443
444
445
446
447
448
449
450
451
452
453
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470
471
472
473
474
475
476
477
478
479
480
481
482
483
484
485
486
487
488
489
490
491
492
493
494
495
496
497
498
499
500
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
517
518
519
520
521
522
523
524
525
526
527
528
529
530
531
532
533
534
535
536
537
538
539
540
541
542
543
544
545
546
547
548
549
550
551
552
553
554
555
556
557
558
559
560
561
562
563
564
565
566
567
568
569
570
571
572
573
574
575
576
577
578
579
580
581
582
583
584
585
586
587
588
589
590
591
592
593
594
595
596
597
598
599
600
601
602
603
604
605
606
607
608
609
610
611
612
613
614
615
616
617
function [HST,TOT,AEQ,Current_ageing,ASUM,Ageing_rate,Total_losses_instant]=IEEE_thermal_model(AMB,PUL,TIM)
%% ************************************************************************
% Purpose: This function represents the thermal model of power transformer
% as given in Annex G of IEEE loading guide C.57.91
%% ************************************************************************
%% Information on code version
% V1.1 17/09/2022 prepared by Ildar DAMINOV based on IEEE C.57.91 Annex G
% Version history
% v1.0 - this version corresponds to IEEE C.57.91 Annex G
% v1.1 - this version is a same as v.1.0 but also includes the
% 'Total_losses_instant' representing the profile of total losses
% inside of transformer. This parameter is validated partially for
% load conditons mentioned in IEEE C.57.91 (28000 kVA, page 85)
% The code was done for the paper (may be used for citation):
% Ildar Daminov, Anton Prokhorov, Raphael Caire, Marie-Cécile Alvarez-Herault,
% "Receding horizon control application for dynamic transformer ratings in
% a real-time economic dispatch," IEEE PES Powertech, Milan, Italy, 2019,
% DOI: https://doi.org/10.1109/PTC.2019.8810511
% Input of IEEE_thermal_model.m:
% AMB - ambient temperature profile in degC; e.g.[24x1] or [1440x1]
% PUL - load profile in per units; e.g.[24x1] or [1440x1]
% TIM - time values in hours
% Output of IEEE_thermal_model.m:
% HST - hot spot temperature profile, degC
% TOT - top oil temperature profile, degC
% AEQ - ageing equivalent for given period, pu
% Current_ageing - a profile of accumulated ageing at given time moment, pu
% ASUM - equivalent ageing, hours
% Ageing_rate - ageing_rate at given moment of time, pu
% Total_losses_instant - profile of total losses at given moment
% Author contacts:
% Linkedin - https://www.linkedin.com/in/ildar-daminov/
% Researchgate - https://www.researchgate.net/profile/Ildar-Daminov-2
% GitHub - https://github.com/Ildar-Daminov
%% Input data processing
% Ensuring the column vector
if (size(PUL,2) > size(PUL,1)) % If number of columns > number of rows
PUL = PUL';
end
if (size(AMB,2) > size(AMB,1)) % If number of columns > number of rows
AMB = AMB';
end
if (size(TIM,2) > size(TIM,1)) % If number of columns > number of rows
TIM = TIM';
end
%% Transformer data from Annex G
XKVA1=28000; % KVA base for losses in input data
TKVA1=75; % Temperature base for losses at this KVA, degC
PW=51690; % I2R losses, W
PE=0; % Winding eddy losses, W
PS=21078; % Stray losses, W
PC=36986; % Core loss, W
XKVA2=52267; % One per unit kVA base for load cycle
THKVA2=65; % Rated ave. winding rise over ambient at kVA base of load cycle, degC
THEWA=63; % Tested or rated average rise over ambient,degC
THEHSA=80; % Winding hottest-spot rise over ambient, degC
THETOR=55; % Top fluid rise over ambient at rated load, C
THEBOR=25; % Bottom fluid rise over ambient at rated load, degC
TAR=30; % Rated ambient at kVA base for load cycle, degC
MC=2; % Winding conductor 1=aluminum, 2=copper
PUELHS=0; % Per unit eddy loss at winding hot-spot location (per unit of I2R loss)
TAUW=5; % Winding time constant, minutes
HHS=1; % Per unit of winding height to hot spot location
WCC=75600; % Weight of core and coils, lb
WTANK=31400; % Weight of tank and fittings, lb
MF=1; % Type of fluid, 1=oil, 2=silicone, 3=HTHC
GFLUID=4910; % Gallons of fluid
MCORE=0; % Overexcitation occurs, 0=no, 1=yes
TIMCOR=0; % Time when overexcitation occurs,h
PCOE=36986; % Core loss during overexcitation, W
%LCAS=1; % Loading case 1(Load cycle repeats and initial Temperatures are unknown) or 2 (Temperatures are inputs) HERE IT IS FOR CASE1
MA=2; % Cooling code 1=ONAN, 2=ONAF, 3=non directed OFAF, 4=directed ODAF
MPR1=0; % Print temperature 1=yes 2=no
DTP=60; % Time increment for printing, minutes
JJ=length(TIM); % Number of points on load cycle
resolution=2; % Choosing time resolutin of output: 1: hour 2: minute
%load data_IEEE_thermal_model;
%TIMP=zeros(KK,1);
%% Additional input data calculation
if JJ==1440
% do nothing
TIM_min=1:TIM(end);
else % ~(JJ==1440)
for i=1:JJ
% Converting hours to minutes
TIM(i)=60.*TIM(i);
end
TIM_min=1:TIM(end);
end
PT=PW+PE+PS+PC; % Total losses at xkva1 (28 000 kVA)
if MPR1==1 % if printing is permitted
fprintf('KVA base for loss input data %d \n',XKVA1)
fprintf('Temperature base for loss input data %d degC \n',TKVA1)
fprintf('Winding I square R %d watts \n',PW)
fprintf('Winding eddy loss %d watts \n',PE)
fprintf('Stray losses %d watts \n',PS)
fprintf('Core losses %d watts \n',PC)
fprintf('Total losses %d watts \n',PT)
end
if MC==1 % Winding conductor choice 1-Al; 2-Cu;
if MPR1==1 % if printing is permitted
fprintf('Winding conductor is aluminium \n')
end
TK=225; % Temperature factor for resistance correction, degC
CPW=6.798; % Specific heat of winding material W-min/lb degC
else % if winding conductor is made of copper;
if MPR1==1 % if printing is permitted
fprintf('Winding conductor is copper \n')
end
TK=234.5; % Temperature factor for resistance correction, degC
CPW=2.91; % Specific heat of winding material W-min/lb degC
end
if MPR1==1 % if printing is permitted
fprintf('Per unit eddy loss at hot spot location %d \n', PUELHS)
fprintf('Winding time constant %d minutes \n', TAUW)
fprintf('Per unit winding height to hot spot %d \n', HHS)
fprintf('Weight of core & coils %d \n', WCC)
fprintf('Weight of tank and fittings %d pounds \n', WTANK)
fprintf('Gallons of fluid %d \n', GFLUID)
end
if MF==1 % If type of fluid is 1=oil
if MPR1==1 % if printing is permitted
fprintf('Cooling fluid is transformer oil\n')
end
CPF=13.92; % Specific heat of fluid, W-min/lb degC
RHOF=0.031621; % Fluid density, lb/in3
C=2797.3; % Constant in viscosity equation
B=0.0013473; % Constant in viscosity equation
else if MF==2 % If type of fluid is 2=silicon
if MPR1==1 % if printing is permitted
fprintf('Cooling fluid is silicon\n')
end
CPF=11.49; % Specific heat of fluid, W-min/lb degC
RHOF=0.0347; % Fluid density, lb/in3
C=1782.3; % Constant in viscosity equation
B=0.12127; % Constant in viscosity equation
else if MF==3 % If type of fluid is 3=HTHC
if MPR1==1 % if printing is permitted
fprintf('Cooling fluid is HTHC\n')
end
CPF=14.55; % Specific heat of fluid, W-min/lb degC
RHOF=0.03178; % Fluid density, lb/in3
C=4434.7; % Constant in viscosity equation
B=7.343e-05; % Constant in viscosity equation
end
end
end
if MA==1 % if Cooling is 1=ONAN,
X=0.5; % Exponent for duct oil rise over bottom oil
YN=0.8; % Exponent of average fluid rise with heat loss
Z=0.5; % Exponent for top to bottom fluid temperature difference
THEDOR=THETOR; % Temperature rise of fluid at top of duct over ambient at rated load
else if MA==2 % if Cooling is 2=ONAF
X=0.5;
YN=0.9;
Z=0.5;
THEDOR=THETOR;
else if MA==3 % If Cooling is 3=non directed OFAF
X=0.5;
YN=0.9;
Z=1;
THEDOR=THEWA;
else if MA==4 % if cooling is 4=directed ODAF
X=1;
YN=1;
Z=1;
THEDOR=THETOR;
end
end
end
end
TWR=TAR+THKVA2; % Rated Average winding temperature at rated load, °C
TWRT=TAR+THEWA; % Average winding temperature at rated load tested, °C
THSR=TAR+THEHSA; % Winding hottest-spot temperature at rated load, °C
TTOR=TAR+THETOR; % Top fluid temperature in tank and radiator at rated load, °C
TBOR=TAR+THEBOR; % Bottom fluid temperature at rated load, °C
TTDOR=THEDOR+TAR; % Fluid temperature at top of duct at rated load, °C
TWOR=(HHS*(TTDOR-TBOR))+TBOR; % Temperature of oil adjacent to winding hot spot at rated load, °C
TDAOR=(TTDOR+TBOR)/2;% Average temperature of fluid in cooling ducts at rated load, °C
TFAVER=(TTOR+TBOR)/2; % Average fluid temperature in tank and radiator at rated load, °C
XK2=(XKVA2/XKVA1)^2;% Ratio between rated power and power used for losses measurement
TK2=(TK+TWR)/(TK+TKVA1);% Temperature factor for resistance correction, °C
PW=XK2*PW*TK2; % full load I2R losses at 75 degC,W
PE=XK2*PE/TK2; % full load eddy losses at 75 degC,W
PS=XK2*PS/TK2; % Stray losses at rated load, W
PT=PW+PE+PS+PC;% Total losses at rated load, W
if (PE/PW)>PUELHS %If ratio of eddy to I2R losses is greater than eddy loss at winding hot spot location
PUELHS=PE/PW; % Eddy loss at winding hot spot location, per unit of I2R loss
end
TKHS=(THSR+TK)/(TWR+TK); % Correction factor for correction of losses to hot-spot temperature
PWHS=TKHS*PW; % Winding I2R loss at rated load and rated hot-spot temperature, W
PEHS=PUELHS*PWHS;% Eddy loss of windings at rated load and rated winding hot-spot temperature,W
% Printing results
if MPR1==1 % if printing is permitted
fprintf('At this KVA losses at %d degC are as follows \n', TWR)
fprintf('Winding I square R %d watts \n',PW)
fprintf('Winding eddy loss %d watts \n',PE)
fprintf('Stray losses %d watts \n',PS)
fprintf('Core losses %d watts \n',PC)
fprintf('Total losses %d watts \n',PT)
fprintf('At this KVA input data for temperatures as follows: \n')
fprintf('Rated average winding rise over ambient %d degC \n',THKVA2)
fprintf('Tested average winding rise over ambient %d degC \n',THEWA)
fprintf('Hottest spot rise over ambient %d degC \n',THEHSA)
fprintf('Top fluid rise over ambient %d degC \n',THETOR)
fprintf('Bottom fluid rise over ambient %d degC \n',THEBOR)
fprintf('Rated ambient temperature %d degC \n',TAR)
end
DT=0.5; % Time step used to calculate thermal mode, min
% Note that there is no problem if DT is different than time step of
% load profile. DT is needed for internal calculations
% For the computer program, a time increment Dt = 0.5 min is used, and
% the following criteria used for stability andaccuracy for all four cooling modes:
DT= TAUW_DT(DT,TAUW); % Function
XMCP=(PE+PW)*TAUW/(TWRT-TDAOR); % Winding mass times specific heat, W-min/°C
WWIND=XMCP/CPW; % Mass of windings, lb
if WWIND>WCC %If Mass of windings is higher than Weight of core and coils
disp ('Winding constant is too high')
disp ('Change input to lower value')
end
WCORE=WCC-WWIND; % Mass of core, lb
CPST=3.51; % Specific heat of steel, W-min/lb degC
WFL=GFLUID*231*RHOF; % Mass of fluid, lb
SUMMCP=(WTANK*CPST)+(WCORE*CPST)+(WFL*CPF); % Total mass times specific heat of fluid, tank, and core, W-min/degC
T1=(TWRT+TDAOR)/2; % Temperature to calculate viscosity, degC
VISR=B*exp(C/(T1+273)); % Viscosity of fluid for average winding temperature rise at rated load, cP
T2=(THSR+TWOR)/2; % Temperature to calculate viscosity, °C
VIHSR=B*exp(C/(T2+273));% Viscosity of fluid for hot-spot calculation at rated load, cP
TMP=0; % Time to print a calculation, min
% if MPR1<1
% DTP=15
% end
KK=fix((TIM(JJ)/DTP)+0.01); % Number of times results are printed
for K=1:KK
TMP=TMP+DTP; % Time to print a calculation, min
TIMP(K,1)=TMP;% Times when results are printed, min
end
THS=THSR; % Winding hottest-spot temperature, degC
TW=TWRT; % Average winding temperature, degC
TTO=TTOR; % Top fluid temperature in tank and radiator, °C
TTDO=TTDOR; % Fluid temperature at top of duct, °C
TBO=TBOR; % Bottom fluid temperature, °C
PR=0; % given in intial program but not used in this function
JLAST=2; % given in intial program but not used in this function
TFAVE=(TTO+TBO)/2; % Average fluid temperature in tank and radiator, degC
TWO=TBO+(HHS*(TTDO-TBO)); % Temperature of oil adjacent to winding hot spot, degC
%% First iteration
THSMAX=THS; % Maximum hottest-spot temperature during load cycle, degC
TIMHS=0; % Time during load cycle when maximum hot spot occurs, h
TTOMAX=TTO; % Maximum top fluid temperature in tank during load cycle, °C
TIMTO=0; % Time during load cycle when maximum top oil temperature occurs, h
J=1; % point on load cycle
K=1; % KK - Number of times results are printed
TIMS=0; % Elapsed time, min
TIMSH=0; % Elapsed time, h
ASUM=0; % Equivalent insulation aging over load cycle, h
HTS=zeros(length(TIMP),1); % Creating zero array for HST calculation
% Total_losses=zeros(length(TIMP),1); Creating zero array for Losses calculation
%QWE=zeros(2*length(TMP),1);
PU_Load=zeros(KK,1);% Creating zero array for PU_load calculation
AMB_Temp= zeros(KK,1); % Creating zero array for AMB calculation
TOPO=zeros(KK,1);% Creating zero array for Temperature top oil calculation
TOPDO=zeros(KK,1);
BOTO=zeros(KK,1);
Time_hours=zeros(KK,1);
HST=zeros(length(PUL),1);
TOT=zeros(length(PUL),1);
Total_losses_instant=zeros(length(PUL),1);
i=0;
ind=1;
while ~(TIMS>TIM(JJ))
if TIMS<TIMP(K)
TIMS=TIMS+DT; % Calculation of elapsed time, min
i=i+1;
if TIMS>TIM(J+1)
J=J+1;
end
TIMSH=TIMS/60; % Calculation of elapsed time in hours
if abs(TIM(J+1)-TIM(J))<0.01
J=J+1;
end
SL=(PUL(J+1)-PUL(J))/(TIM(J+1)-TIM(J)); %Slope of line between two load points of load cycle curve
PL=PUL(J)+(SL*(TIMS-TIM(J))); % ratio of load L to rated load, per unit
SLAMB=(AMB(J+1)-AMB(J))/(TIM(J+1)-TIM(J));% Slope of line between two ambient temperature points of load cycle curve
TA=AMB(J)+(SLAMB*(TIMS-TIM(J)));% Ambient temperature, degC
TDAO=(TTDO+TBO)/2;% Average temperature of fluid in cooling ducts, °C
TKW=(TW+TK)/(TWR+TK); %Temperature correction for losses of winding
QWGEN=PL.*PL.*((TKW.*PW)+(PE./TKW)).*DT;%Heat generated by windings, W-min
if TW<TDAO % if mean winding temperature is less than mean temperature of fluid in cooling ducts
QWLOST=0;% Heat lost by winding, W-min
if TW<TBO % if average winding temperature is less than Bottom fluid temperature
TW=TBO;% average winding temperature , deg C
end
else %TW>=TDAO
if MA==1 || MA==2 || MA==3 %if Cooling code (MA) is 1=ONAN, 2=ONAF or 3=non directed OFAF,
T=(TW+TDAO)/2; % Temperature to calculate viscosity, degC
VIS= B*exp(C/(T+273)); % Viscosity of fluid for average winding temperature rise calc., cP
QWLOST=(((TW-TDAO)./(TWRT-TDAOR)).^1.25)*((VISR./VIS).^0.25)*(PW+PE)*DT; % Heat lost by winding, W-min
else
QWLOST=((TW-TDAO)./(TWRT-TDAOR))*(PW+PE)*DT; %# Heat lost by winding, W-min
end
end
TW=(QWGEN-QWLOST+(XMCP*TW))/XMCP;% Average winding temperature, °C
DTDO=(TTDOR-TBOR)*((QWLOST/((PW+PE)*DT))^X);%Temperature rise of fluid at top of duct over bottom fluid, °C
TTDO=TBO+DTDO;% Fluid temperature at top of duct, °C
TDAO=(TTDO+TBO)/2; % Average temperature of fluid in cooling ducts, °C
TWO=TBO+(HHS*DTDO);%Temperature of oil adjacent to winding hot spot, °C
TKHS=(THS+TK)/(THSR+TK); %Temperature correction for losses at hot spot location
if (TTDO+0.1)<TTO %If Fluid temperature at top of duct is less than Top fluid temperature in tank and radiator
TWO=TTO; % Temperature of oil adjacent to winding hot spot, degC
end
if THS<TW % If winding hot spot temperature is less than average winding temperature
THS=TW; % Winding hottest-spot temperature, degC
end
if THS<TWO %If Winding hottest-spot temperature is less than temperature of oil adjacent to winding hot spot
THS=TWO; % Winding hottest-spot temperature, degC
end
QHSGEN=PL.*PL.*((TKHS.*PWHS)+(PEHS./TKHS)).*DT;%Heat generated at hot spot temperature, W-min
if MA==1 || MA==2 || MA==3 % if Cooling code (MA) is 1=ONAN, 2=ONAF or 3=non directed OFAF,
T=(THS+TWO)/2;%Temperature to calculate viscosity, °C
VISHS=B*exp(C/(T+273));%Viscosity of fluid for hot-spot calculation, cP
QLHS =(((THS-TWO)/(THSR-TWOR))^1.25)*((VIHSR/VISHS)^0.25)*(PWHS+PEHS)*DT;%Heat lost for hot-spot calculation, W-min
else
QLHS=((THS-TWO)/(THSR-TWOR))*(PWHS+PEHS)*DT; % Heat lost for hot-spot calculation, W-min
end
% PW_moment=PW*TKW;
PE_moment=PE/TKW; % full load eddy losses at 75 degC
% PS_moment=PS/TKW;
PW_instant=PL.*PL.*((TKW.*PW)+(PE./TKW)); % Instant I2R losses, W
PS_instant=((PL*PL*PS)/TKW); % Instant stray losses, W
THS=(QHSGEN-QLHS+(XMCP*THS))/XMCP; %Winding hottest-spot temperature, degC
if TIMS==TIM(ind)
HST(ind)=THS;
end
%QWE(i)=THS;
QS=((PL*PL*PS)/TKW)*DT; % Heat generated by stray losses, W-min
QLOSTF=(((TFAVE-TA)/(TFAVER-TAR))^(1/YN))*PT*DT; % Heat lost by fluid to ambient, W-min
if MCORE<1 % Core overexcitation occurs during load cycle, 0 = no, 1 = yes
QC=PC*DT; % Heat generated by core, W-min
elseif TIMS<TIMCOR % If elapsed time is less than Time when core overexcitation occurs, h
QC=PC*DT; % Heat generated by core, W-min
else % TIMS > = TIMCOR:
QC=PCOE*DT; % Heat generated by core, W-min
end
TFAVE=(QWLOST+QC+QS-QLOSTF+(SUMMCP*TFAVE))/SUMMCP;%Average fluid temperature in tank and radiator, °C
DTTB=((QLOSTF/(PT*DT))^Z)*(TTOR-TBOR);%Temperature rise of fluid at top of radiator over bottom fluid, °C
TTO=TFAVE+(DTTB/2); %Top fluid temperature in tank and radiator, °C
if TIMS==TIM(ind)
TOT(ind)=TTO;
Total_losses_instant(ind)=PW_instant+PE_moment+PS_instant+PC;
ind=ind+1;
end
TBO=TFAVE-(DTTB/2);%Bottom fluid temperature, °C
if TBO<TA % If Bottom fluid temperature is less than ambient temperature
TBO=TA; % Bottom fluid temperature, degC
end
if TTDO<TBO % If Fluid temperature at top of duct is less than Bottom fluid temperature
TTDO=TBO; % Fluid temperature at top of duct,degC
end
AX=(15000/383)-(15000./(THS+273)); % Power of exp (see next line)
A=exp(AX); % Aging acceleration factor
ASUM=ASUM+(A*DT); % Equivalent insulation aging over load cycle, h
if ~(THS<THSMAX) % If Winding hottest temperature is greater or equal to its maximum,registered before
THSMAX=THS; % Maximum hottest-spot temperature during load cycle, degC
end
if ~(TTO<TTOMAX)% If top oil temperature is greater or equal to its maximum
TTOMAX=TTO; % Maximum top fluid temperature in tank during load cycle, degC
end
elseif K<=length(TIMP)
HTS(K)=THS;
% Total_losses(K)=PW_moment+PE_moment+PS_moment+PC;
PU_Load(K)=PL;
Time_hours(K)=TIMSH;
AMB_Temp(K)=TA;
TOPO(K)=TTO;
TOPDO(K)=TTDO;
BOTO(K)=TBO;
if K<KK
K=K+1;
else %K > = JJ
break
end
else % # TIMS >=TIMP(K):
break
end
end
if MPR1==1 % if printing is permitted
fprintf('Time\tPU_Load AMB\t HS\t TOPO\t TOPDO\t BOTO\n')
fprintf('%.2f\t %.2f\t %.2f\t %.2f\t %.2f\t %.2f\t %.2f\t \n',0,PUL(1), AMB(1),HTS(end), TTO(end),TTDO(end),TBO(end))
end
%% Second iteration calculation
Current_ageing=0; % Set current ageing to zero
THSMAX=THS; % Import winding hottest spot temperature from first iteration and set it as THSMAX
TIMHS=0; % Set Time during load cycle when maximum hot spot occurs, h to zero
TTOMAX=TTO; % Import top-oil temperature from first iteration and set it as TTOMAX
TIMTO=0; % Set Time during load cycle when maximum top oil temperature occurs, h to zero
J=1;
K=1;
% Set to zero following parameters:
TIMS=0;
TIMSH=0;
ASUM=0;
HTS=zeros(length(TIMP),1);
%QWE=zeros(2*length(TMP),1);
PU_Load=zeros(KK,1);
AMB_Temp= zeros(KK,1);
TOPO=zeros(KK,1);
TOPDO=zeros(KK,1);
BOTO=zeros(KK,1);
Time_hours=zeros(KK,1);
HST=zeros(length(PUL),1);
TOT=zeros(length(PUL),1);
Total_losses_instant=zeros(length(PUL),1);
HST_min=zeros(length(TIM_min),1);
TOT_min=zeros(length(TIM_min),1);
Total_losses_instant_min=zeros(length(TIM_min),1);
Current_ageing_min=zeros(length(TIM_min),1);
Ageing_rate_min=zeros(length(TIM_min),1);
i=0;
ind=1;
% Recalculate the thermal mode of transformer
while ~(TIMS>TIM(JJ))
if TIMS<TIMP(K)
TIMS=TIMS+DT;
i=i+1;
if TIMS>TIM(J+1)
J=J+1;
end
TIMSH=TIMS/60;
if abs(TIM(J+1)-TIM(J))<0.01
J=J+1;
end
SL=(PUL(J+1)-PUL(J))/(TIM(J+1)-TIM(J)); % Slope of line between two load points of load cycle curve
PL=PUL(J)+(SL*(TIMS-TIM(J))); % ratio of load L to rated load, per unit
SLAMB=(AMB(J+1)-AMB(J))/(TIM(J+1)-TIM(J)); % Slope of line between two ambient temperature points of load cycle curve
TA=AMB(J)+(SLAMB*(TIMS-TIM(J))); % Ambient temperature, degC
TDAO=(TTDO+TBO)/2; % Average temperature of fluid in cooling ducts, degC
TKW=(TW+TK)/(TWR+TK); % Temperature correction for losses of winding
QWGEN=PL.*PL.*((TKW.*PW)+(PE./TKW)).*DT; % Heat generated by windings, W-min
if TW<TDAO % if mean winding temperature is less than mean temperature of fluid in cooling
QWLOST=0; % Heat lost by winding, W-min
if TW<TBO % if average winding temperature is less than Bottom fluid temperature
TW=TBO; % average winding temperature, degC
end
else % TW> = TDAO
if MA==1 || MA==2 || MA==3 % if Cooling code (MA) is 1=ONAN, 2=ONAF or 3=non directed OFAF
T=(TW+TDAO)/2; % Temperature to calculate viscosity, degC
VIS= B*exp(C/(T+273)); % Viscosity of fluid for average winding temperature rise calc., cP
QWLOST=(((TW-TDAO)./(TWRT-TDAOR)).^1.25)*((VISR./VIS).^0.25)*(PW+PE)*DT; % Heat lost by winding, W-min
else
QWLOST=((TW-TDAO)./(TWRT-TDAOR))*(PW+PE)*DT;% Heat lost by winding, W-min
end
end
TW=(QWGEN-QWLOST+(XMCP*TW))/XMCP; % average winding temperature, degC
DTDO=(TTDOR-TBOR)*((QWLOST/((PW+PE)*DT))^X); % Temperature rise of fluid at top of duct over bottom fluid, °C
TTDO=TBO+DTDO; % Fluid temperature at top of duct, °C
TDAO=(TTDO+TBO)/2; % Average temperature of fluid in cooling ducts, °C
TWO=TBO+(HHS*DTDO); % Temperature of oil adjacent to winding hot spot, °C
TKHS=(THS+TK)/(THSR+TK); % Correction factor for correction of losses to hot-spot temperature
if (TTDO+0.1)<TTO
TWO=TTO; % Temperature of oil adjacent to winding hot spot, °C
end
if THS<TW %If winding hot spot temperature is less than average winding temperature
THS=TW; % winding hottest spot temperature
end
if THS<TWO % If Winding hottest-spot temperature is less than temperature of oil adjacent to winding hot spot
THS=TWO; % winding hottest spot temperature
end
QHSGEN=PL.*PL.*((TKHS.*PWHS)+(PEHS./TKHS)).*DT;% Heat generated at hot spot temperature,
if MA==1 || MA==2 || MA==3 % if Cooling code (MA) is 1=ONAN, 2=ONAF or 3=non directed OFAF
T=(THS+TWO)/2;%Temperature to calculate viscosity, degC
VISHS=B*exp(C/(T+273)); % Viscosity of fluid for hot-spot calculation, cP
QLHS =(((THS-TWO)/(THSR-TWOR))^1.25)*((VIHSR/VISHS)^0.25)*(PWHS+PEHS)*DT;%Heat lost for hot-spot calculation, W-min
else % if MA is 4=directed ODAF
QLHS=((THS-TWO)/(THSR-TWOR))*(PWHS+PEHS)*DT; %Heat lost for hot-spot calculation, W-min
end
% PW_moment=PW*TKW;
PE_moment=PE/TKW; % full load eddy losses at 75 degC
% PS_moment=PS/TKW;
PW_instant=PL.*PL.*((TKW.*PW)+(PE./TKW)); % Instant I2R losses, W
PS_instant=((PL*PL*PS)/TKW); % Instant stray losses, W
THS=(QHSGEN-QLHS+(XMCP*THS))/XMCP;% Winding hottest-spot temperature, degC
if TIMS==TIM(ind)
HST(ind)=THS;
end
QS=((PL*PL*PS)/TKW)*DT;%Heat generated by stray losses, W-min
QLOSTF=(((TFAVE-TA)/(TFAVER-TAR))^(1/YN))*PT*DT; %Heat lost by fluid to ambient, W-min
if MCORE<1%if Core overexcitation does not occur during load cycle, 0 = no, 1 = yes
QC=PC*DT;%Heat generated by core, W-min
elseif TIMS<TIMCOR
QC=PC*DT;%Heat generated by core, W-min
else %TIMS > = TIMCOR:
QC=PCOE*DT;%Heat generated by core, W-min
end
TFAVE=(QWLOST+QC+QS-QLOSTF+(SUMMCP*TFAVE))/SUMMCP;%Average fluid temperature in tank and radiator, °C
DTTB=((QLOSTF/(PT*DT))^Z)*(TTOR-TBOR);%Temperature rise of fluid at top of radiator over bottom fluid, °C
TTO=TFAVE+(DTTB/2);%Top fluid temperature in tank and radiator, °C
if TIMS==TIM(ind)
TOT(ind)=TTO;
Total_losses_instant(ind)=PW_instant+PE_moment+PS_instant+PC;
ind=ind+1;
end
TBO=TFAVE-(DTTB/2);%Bottom fluid temperature, °C
if TBO<TA%If Bottom fluid temperature is less than Ambient temperature
TBO=TA;%Bottom fluid temperature, °C
end
if TTDO<TBO %If Fluid temperature at top of duct is less than Bottom fluid temperature
TTDO=TBO;%Fluid temperature at top of duct, degC
end
AX=(15000/383)-(15000./(THS+273)); %Power of exp (see next line)
A=exp(AX);%Ageing acceleration factor
ASUM=ASUM+(A*DT);%Equivalent insulation aging over load cycle, h
if ismember(TIMS,TIM_min) % min resolution
ind_min=find(TIM_min==TIMS);
HST_min(ind_min,1)=THS;
TOT_min(ind_min,1)=TTO;
Total_losses_instant_min(ind_min,1)=PW_instant+PE_moment+PS_instant+PC;
Current_ageing_min(ind_min,1)=ASUM/(TIM_min(end));
Ageing_rate_min(ind_min,1)=A';
end
if ~(THS<THSMAX)% If Winding hottest temperature is greater or equal to its maximum,registered before
THSMAX=THS; % Maximum hottest-spot temperature during load cycle, degC
TIMHS=TIMSH;% Time during load cycle when maximum hot spot occurs
end
if ~(TTO<TTOMAX)%If top oil temperature is greater or equal to its maximum
TTOMAX=TTO; %Maximum top fluid temperature in tank during load cycle, degC
TIMTO=TIMSH;%Time during load cycle when maximum top oil temperature occurs, h
end
elseif K<=length(TIMP)
HTS(K)=THS;
% Current_ageing(K)=ASUM/60/length(PUL); % Ageing to particular moment
Current_ageing(K)=ASUM/(TIM(end));
Ageing_rate(K)=A';
PU_Load(K)=PL;
Time_hours(K)=TIMSH;
AMB_Temp(K)=TA;
TOPO(K)=TTO;
TOPDO(K)=TTDO;
BOTO(K)=TBO;
if K<KK
K=K+1;
else
break
end
else
break
end
end
if (size(Current_ageing,2) > size(Current_ageing,1)) % If number of columns > number of rows
Current_ageing = Current_ageing';
end
% ASUM=ASUM/60;%Equivalent insulation aging over load cycle, h
AEQ=ASUM/TIM(end);%Equivalent aging acceleration factor over a complete load cycle
%% Printing the second iteration results
if MPR1==1 % if printing is permitted
for K=1:KK
if K<=KK-1
fprintf('%.2f\t %.2f\t %.2f\t %.2f\t %.2f\t %.2f\t %.2f\t \n',Time_hours(K), PU_Load(K), AMB_Temp(K), HTS(K), TOPO(K), TOPDO(K), BOTO(K))
elseif K==KK
fprintf('%.2f\t %.2f\t %.2f\t %.2f\t %.2f\t %.2f\t %.2f\t \n',Time_hours(K),PUL(1), AMB(1),HTS(end), TTO(end),TTDO(end),TBO(end))
end
end
fprintf ('Temperature during load cycle\n')
fprintf ('MAX.HOT SPOT TEMP.= %f AT %0.5f HOURS\n',THSMAX,TIMHS)
fprintf ('MAX. TOP FLUID TEMP.= %f AT %0.5f HOURS\n',TTOMAX,TIMTO)
fprintf ('FINAL HOT SPOT TEMP.= %f\n',THS)
fprintf ('FINAL AVE. WIND. TEMP.= %f\n', TW)
fprintf ('FINAL TOP OIL TEMP.= %f\n', TTO)
fprintf ('FINAL TOP DUCT OIL TEMP.= %f\n', TTDO)
fprintf ('FINAL BOT. OIL TEMP.= %f\n', TBO)
fprintf ('EQUIVALENT AGING = %f HOURS\n', ASUM)
fprintf ('LOAD CYCLE DURATION = %f\n',TIMSH)
fprintf ('EQUIVALENT AGING FACTOR =%f\n', AEQ)
figure (1)
hax=plotyy(Time_hours,HTS,Time_hours,PU_Load);
legend({'HST','PUL'});
grid on
xlabel('Time');
ylabel (hax(1),'HST');
ylabel (hax(2),'PU load');
title (['Hot spot temperature with EAF=',num2str(AEQ)]);
end
%% Choosing the time resolution of output
if resolution==2 % minute resolution is chosen
% Changing the output variable
HST=HST_min;
TOT=TOT_min;
Current_ageing=Current_ageing_min;
Ageing_rate=Ageing_rate_min;
Total_losses_instant=Total_losses_instant_min;
end % end of if resolution==2
end % end of IEEE_thermal_model.m